Inzonex← The condensate lineYour calculated result
Y-strainers, uninsulatedY-strainers, insulated by Inzonex
05 / Equipment
Without insulationWith removable insulation
‹›
Y-strainers448 Wbare19 Winsulated95.8 %less
Drag to compare
Views

Inzonex Modular Insulation · Condensate line

Condensate Y-strainers

Estimate for one condensate line:

The figures initially displayed are example scenarios.

Energy cost saving / year€22960 €/MWh fuel
Energy saved per year3.4 MWhAt 8,000 operating hours
Estimated emissions avoided0.77 t CO₂e201.6 kg CO₂e/MWh fuel
Modelled outer surface27.3 °CBelow the 45 °C design target

Estimate: 110 °C bare surface · 8,000 operating hours/year.

€229energy cost saving / year3.4 MWhretained

01 / For your operating conditions

Your calculated result

Change any input and every figure recomputes. The defaults describe the equipment modelled here.

°C
m²
h/yr
mm
°C
€/MWh
€

02 / Result

What it comes to.

Outer surface at 50 mm
27.3 °CMeets the 45 °C design target
Bare metal at 110 °C
Above the 45 °C insulated-surface design targetContact risk depends on material and duration; no burn time is calculated
Average payback
Enter your installed cost to calculate payback.

03 / Questions

Questions.

How much heat do the Y-strainers lose on a condensate line?

Modelled here: at 110 °C they lose 448 W bare, and 19 W with 50 mm of removable insulation. That is 95.8 per cent less.

Where does the area come from?

The default is a provisional reference area, not a measured area for this model. Automatic DN lookup is unavailable until construction and pressure class are confirmed. Enter the verified external hot area, including physical fasteners where present. Exclude cold actuators and avoid counting shared surfaces twice.

Is it safe to touch once insulated?

The module settles at 27.3 °C on these defaults, under our 45 °C insulated-surface design target. We set that target against the burn thresholds in EN ISO 13732-1.

04 / Method

How the figure is produced.

Calculation basis
Steady-state estimate based on the dimensions and operating conditions shown. Confirm project figures with measured equipment data.

Insulated surface: up to 45 °C.

05 / The rest of the line

Other equipment

06 / Scenarios

Area at each service temperature.

Bare surface loss per item. Nothing here is interpolated — each cell is a separate solution of the same balance, at 20 °C ambient.

Reference scenario100 °C110 °C125 °C140 °CInsulated 110 °CCut
Area scenario 1Not a product size149 W174 W215 W259 W7 W95.8 %
Area scenario 2Not a product size167 W195 W240 W290 W8 W95.8 %
Area scenario 3Not a product size191 W224 W276 W332 W9 W95.8 %
Area scenario 4Not a product size228 W267 W329 W396 W11 W95.8 %
Area scenario 5Not a product size256 W300 W370 W445 W13 W95.8 %
Area scenario 6Not a product size319 W373 W460 W554 W16 W95.8 %
Area scenario 7Not a product size394 W461 W569 W685 W19 W95.8 %
Area scenario 8Not a product size503 W588 W725 W874 W25 W95.8 %
Area scenario 9Not a product size709 W829 W1.0 kW1.2 kW35 W95.8 %
Area scenario 10Not a product size955 W1.1 kW1.4 kW1.7 kW47 W95.8 %
Area scenario 11Not a product size1.3 kW1.5 kW1.8 kW2.2 kW63 W95.8 %
Area scenario 12Not a product size2.0 kW2.3 kW2.9 kW3.4 kW98 W95.8 %
Area scenario 13Not a product size2.9 kW3.4 kW4.2 kW5.0 kW143 W95.8 %

Illustrative areas, not verified DN-to-area mappings for this equipment. Replace the input with measured external geometry for a project calculation. Physical bolt, nut, flange and stem coverage must be checked separately.

Insulated column: 50 mm lamella at λ 0.038 W/m·K. Outer surface calculated without clamping. Our 45 °C design target is checked against the burn thresholds in EN ISO 13732-1