InzonexIndustrial Heat-Loss Calculator

Heat-Loss Calculator › Reference tables

Pipe heat-loss reference tables

Bare vs. insulated heat loss (W/m), touch-safe surface temperature, annual CO₂ and removable-insulation payback for common steel pipe sizes and temperatures, by the ASTM C680 method. Pick a size and temperature, or open the full calculator.

Size120°C150°C180°C200°C250°C300°C350°C
DN25
1″
105
W/m bare
136
W/m bare
168
W/m bare
189
W/m bare
241
W/m bare
294
W/m bare
346
W/m bare
DN40
1½″
152
W/m bare
197
W/m bare
243
W/m bare
273
W/m bare
349
W/m bare
425
W/m bare
501
W/m bare
DN50
2″
189
W/m bare
246
W/m bare
303
W/m bare
341
W/m bare
436
W/m bare
530
W/m bare
625
W/m bare
DN65
2½″
239
W/m bare
311
W/m bare
383
W/m bare
430
W/m bare
550
W/m bare
669
W/m bare
789
W/m bare
DN80
3″
279
W/m bare
363
W/m bare
447
W/m bare
503
W/m bare
642
W/m bare
782
W/m bare
922
W/m bare
DN100
4″
359
W/m bare
467
W/m bare
575
W/m bare
646
W/m bare
826
W/m bare
1005
W/m bare
1185
W/m bare
DN125
5″
439
W/m bare
571
W/m bare
702
W/m bare
790
W/m bare
1009
W/m bare
1229
W/m bare
1448
W/m bare
DN150
6″
529
W/m bare
687
W/m bare
846
W/m bare
952
W/m bare
1216
W/m bare
1480
W/m bare
1745
W/m bare
DN200
8″
688
W/m bare
895
W/m bare
1101
W/m bare
1239
W/m bare
1583
W/m bare
1927
W/m bare
2271
W/m bare

Need a whole-plant total?

Add every pipe, valve, tank and vessel into one project for a site-wide energy, cost and CO₂ total — then get a fixed insulation price.