InzonexIndustrial Heat-Loss Calculator

Heat-Loss CalculatorReference › DN80 (3″) @ 150°C

Heat loss from a DN80 (3″) pipe at 150 °C

A bare DN80 (3″) pipe running at 150 °C in 20 °C still air loses about 363 W per metre. Wrap it in 50 mm of removable lamella mat and loss drops to about 56 W/m — a 85% cut — while the outer surface falls to about 29 °C (touch-safe). Figures use the ASTM C680 steady-state method.

These conditions are typical of low-pressure saturated steam, medium-temperature hot water (MTHW) and thermal-oil return lines. A bare surface here is already a burn risk and loses a large, continuous amount of heat that insulation recovers almost entirely.

Per-metre heat loss

QuantityBareInsulated (50 mm)
Heat loss363 W/m56 W/m
Heat loss (imperial)377.7 BTU/hr·ft57.9 BTU/hr·ft
Reduction85%
Outer surface temp~150°C29°C
Conductivity k (at 85°C mean)0.055 W/m·K

How much insulation thickness?

The same DN80 (3″) line at 150 °C, with different removable-insulation thicknesses (lamella mat, k≈0.055 W/m·K). Heat loss and surface temperature both fall as thickness increases — with diminishing returns past 50–75 mm.

ThicknessHeat lossReductionSurface temp
25 mm86 W/m76%40°C
40 mm64 W/m82%32°C
50 mm56 W/m85%29°C
75 mm44 W/m88%26°C
100 mm37 W/m90%24°C

At this temperature the bare surface burns on contact within a second; 50 mm of removable insulation typically returns it to a touch-safe ≤45 °C.

Example: a 50 m line with 4 valves

ResultValue
Heat loss, bare19.0 kW
Heat saved by insulation16.1 kW
Fuel energy saved151.6 MWh/yr
Money saved€10,611/yr
CO₂ avoided30.3 t/yr (≈ 6.6 cars off the road, 1,444 trees, 6.3 homes’ power, 70 barrels of oil, 124,150 km of driving or 30 transatlantic flights)
Payback (removable insulation)8.8 months

Assumptions. 50 m pipe + 4 valves (each ≈0.6 m bare pipe), 8000 h/yr, 85% boiler efficiency, €0.07/kWh fuel, 0.20 kg CO₂/kWh, 50 mm insulation at €250/m². CO₂ equivalences use US EPA / DEFRA conversion factors. Change any of these in the live calculator. Estimates for guidance — confirm with a site survey.

Run your own numbers

Adjust size, temperature, thickness, hours and energy price live — or get an exact heat-loss study and fixed insulation price for your equipment list.

Open the calculator →Get an exact quote

Is a bare DN80 (3″) line at 150 °C a burn hazard?

Yes — a bare DN80 (3″) surface at 150 °C exceeds the ~60 °C touch-safe threshold (ASTM C1055, EN ISO 13732-1) and burns on brief contact. The line also loses about 363 W/m, so insulation fixes safety and energy at once.

Related heat-loss tables

DN80 @ 120°CDN80 @ 180°CDN80 @ 200°CDN80 @ 250°CDN80 @ 300°CDN80 @ 350°CDN25 @ 150°CDN40 @ 150°CDN50 @ 150°CDN65 @ 150°CDN100 @ 150°CDN125 @ 150°CDN150 @ 150°CDN200 @ 150°CAll tables →