InzonexIndustrial Heat-Loss Calculator

Heat-Loss CalculatorReference › DN125 (5″) @ 150°C

Heat loss from a DN125 (5″) pipe at 150 °C

A bare DN125 (5″) pipe running at 150 °C in 20 °C still air loses about 571 W per metre. Wrap it in 50 mm of removable lamella mat and loss drops to about 77 W/m — a 86% cut — while the outer surface falls to about 30 °C (touch-safe). Figures use the ASTM C680 steady-state method.

These conditions are typical of low-pressure saturated steam, medium-temperature hot water (MTHW) and thermal-oil return lines. A bare surface here is already a burn risk and loses a large, continuous amount of heat that insulation recovers almost entirely.

Per-metre heat loss

QuantityBareInsulated (50 mm)
Heat loss571 W/m77 W/m
Heat loss (imperial)593.5 BTU/hr·ft80.3 BTU/hr·ft
Reduction86%
Outer surface temp~150°C30°C
Conductivity k (at 85°C mean)0.055 W/m·K

How much insulation thickness?

The same DN125 (5″) line at 150 °C, with different removable-insulation thicknesses (lamella mat, k≈0.055 W/m·K). Heat loss and surface temperature both fall as thickness increases — with diminishing returns past 50–75 mm.

ThicknessHeat lossReductionSurface temp
25 mm124 W/m78%41°C
40 mm90 W/m84%33°C
50 mm77 W/m86%30°C
75 mm59 W/m90%26°C
100 mm49 W/m91%25°C

At this temperature the bare surface burns on contact within a second; 50 mm of removable insulation typically returns it to a touch-safe ≤45 °C.

Example: a 50 m line with 4 valves

ResultValue
Heat loss, bare29.9 kW
Heat saved by insulation25.9 kW
Fuel energy saved243.3 MWh/yr
Money saved€17,031/yr
CO₂ avoided48.7 t/yr (≈ 10.6 cars off the road, 2,317 trees, 10.1 homes’ power, 113 barrels of oil, 199,265 km of driving or 49 transatlantic flights)
Payback (removable insulation)7.0 months

Assumptions. 50 m pipe + 4 valves (each ≈0.6 m bare pipe), 8000 h/yr, 85% boiler efficiency, €0.07/kWh fuel, 0.20 kg CO₂/kWh, 50 mm insulation at €250/m². CO₂ equivalences use US EPA / DEFRA conversion factors. Change any of these in the live calculator. Estimates for guidance — confirm with a site survey.

Run your own numbers

Adjust size, temperature, thickness, hours and energy price live — or get an exact heat-loss study and fixed insulation price for your equipment list.

Open the calculator →Get an exact quote

Is a bare DN125 (5″) line at 150 °C a burn hazard?

Yes — a bare DN125 (5″) surface at 150 °C exceeds the ~60 °C touch-safe threshold (ASTM C1055, EN ISO 13732-1) and burns on brief contact. The line also loses about 571 W/m, so insulation fixes safety and energy at once.

Related heat-loss tables

DN125 @ 120°CDN125 @ 180°CDN125 @ 200°CDN125 @ 250°CDN125 @ 300°CDN125 @ 350°CDN25 @ 150°CDN40 @ 150°CDN50 @ 150°CDN65 @ 150°CDN80 @ 150°CDN100 @ 150°CDN150 @ 150°CDN200 @ 150°CAll tables →