Inzonex← Visual Heat ExplorerStart calculation
ISO 12241 Table A.3

Gate-valve reference areas from DN15 to DN200

The equivalent area includes the valve body, flanges, bolts and stem. No additional bare-area allowance is applied. DN250 remains available for pipe and entered CAD areas, but is not presented as an ISO gate-valve value.

SizePipe OD mmEquivalent area m²Face-to-face mmFlange Ø mmBolts / jointBare loss at 180 °C
DN1521.30.1115130954 × M12319 W
DN2026.70.12491501054 × M12356 W
DN2533.40.14341601154 × M12406 W
DN3242.20.17091801404 × M16480 W
DN4048.30.19212001504 × M16538 W
DN5060.30.23882301654 × M16666 W
DN6573.00.29542901854 × M16821 W
DN8088.90.37693102008 × M161.04 kW
DN100114.30.53153502208 × M161.47 kW
DN125139.70.71604002508 × M161.97 kW
DN150168.30.95954802858 × M202.63 kW
DN200219.11.485760034012 × M204.05 kW
DN250273.0Not tabulated73040512 × M24Enter measured area

Area source: ISO 12241:2022 Annex A.2.3 Table A.3. Dimensions shown for identification use the current EN 558 and EN 1092-1 PN16 reference table. Manufacturer dimensions take precedence.