λ = 0.055 W/m·K at mean temperature ((200+20)/2 = 110 °C, from the published curve). Pipe losses per metre, four thicknesses, savings vs bare.
| Pipe | 30 mm W/m | 50 mm W/m | 80 mm W/m | 100 mm W/m | BARE W/m | Surface @50 mm | Saving €/m·yr @50 mm | t CO2/m·yr |
|---|---|---|---|---|---|---|---|---|
| DN25 | 54 | 42 | 34 | 31 | 189 | 30 °C | €71 | 0.26 |
| DN50 | 80 | 59 | 46 | 41 | 341 | 32 °C | €137 | 0.50 |
| DN80 | 105 | 77 | 58 | 51 | 503 | 33 °C | €208 | 0.76 |
| DN100 | 128 | 91 | 68 | 59 | 646 | 34 °C | €271 | 0.99 |
| DN150 | 176 | 123 | 89 | 77 | 952 | 35 °C | €404 | 1.48 |
| DN200 | 221 | 152 | 108 | 92 | 1,239 | 35 °C | €530 | 1.94 |
| DN300 | 313 | 211 | 147 | 124 | 1,832 | 36 °C | €791 | 2.89 |
Assumptions: 20 °C ambient, still air (h=10 W/m²·K combined), €0.05/kWh fuel, 8000 h/yr, 82% efficiency, 0.183 kg CO2e/kWh (DESNZ 2024). Flat surfaces at this duty: bare 1,800 W/m² → 178 W/m² at 50 mm (≈€791/m²·yr saved). Method: ASTM C680 simplified — methodology. Your exact case: free calculator.
| Material | λ W/m·K | Loss W/m | Surface | Saving €/m·yr | t CO2/m·yr |
|---|---|---|---|---|---|
| Stone wool (mineral wool) | 0.048 | 80 | 32 °C | €276 | 1.0 |
| Glass wool | 0.046 | 77 | 31 °C | €278 | 1.0 |
| Ceramic fibre (RCF / AES blanket) | 0.060 | 99 | 35 °C | €267 | 1.0 |
| Aerogel blanket | 0.026 | 45 | 27 °C | €294 | 1.1 |
| Calcium silicate | 0.063 | 104 | 35 °C | €265 | 1.0 |
| Expanded perlite | 0.066 | 109 | 36 °C | €262 | 1.0 |
| Cellular glass | 0.054 | 89 | 33 °C | €272 | 1.0 |
| Microporous (fumed-silica) panels | 0.022 | 39 | 26 °C | €296 | 1.1 |
| E-glass needle mat | 0.046 | 78 | 32 °C | €277 | 1.0 |
| Silica needle mat / fabric | 0.055 | 91 | 34 °C | €271 | 1.0 |
DN100 pipe at 200 °C, 50 mm insulation, per metre of pipe; bare loss 646 W/m. λ at mean temperature; € and CO2 per metre·year at €0.05/kWh, 8000 h, 82% efficiency. Method: ASTM C680 simplified (h=10).
Material datasheet: Silica needle mat / fabric → · temperature class: by temperature →