Inzonex Insulation Hubpowered by inzonex.co.uk
Insulation HubData tables → Expanded perlite at 250 °C
Computed datasheet

Expanded perlite at 250 °C — heat-loss table

λ = 0.070 W/m·K at mean temperature ((250+20)/2 = 135 °C, from the published curve). Pipe losses per metre, four thicknesses, savings vs bare.

Pipe30 mm W/m50 mm W/m80 mm W/m100 mm W/mBARE W/mSurface @50 mmSaving €/m·yr @50 mmt CO2/m·yr
DN258567555024136 °C€850.31
DN5012594746643639 °C€1660.61
DN80165121938264240 °C€2540.93
DN1002001451099582642 °C€3321.22
DN1502751941411221,21643 °C€4991.82
DN2003442401721471,58344 °C€6552.40
DN3004873332341982,34045 °C€9793.58

Assumptions: 20 °C ambient, still air (h=10 W/m²·K combined), €0.05/kWh fuel, 8000 h/yr, 82% efficiency, 0.183 kg CO2e/kWh (DESNZ 2024). Flat surfaces at this duty: bare 2,300 W/m² → 281 W/m² at 50 mm (≈€985/m²·yr saved). Method: ASTM C680 simplified — methodology. Your exact case: free calculator.

Context

All materials at 250 °C

Materialλ W/m·KLoss W/mSurfaceSaving €/m·yrt CO2/m·yr
Stone wool (mineral wool)0.05211237 °C€3481.3
Glass wool0.05010636 °C€3511.3
Ceramic fibre (RCF / AES blanket)0.06012739 °C€3411.2
Aerogel blanket0.0276129 °C€3731.4
Calcium silicate0.06713941 °C€3351.2
Expanded perlite0.07014542 °C€3321.2
Cellular glass0.05812238 °C€3431.3
Microporous (fumed-silica) panels0.0235027 °C€3781.4
E-glass needle mat0.05010636 °C€3511.3
Silica needle mat / fabric0.05511737 °C€3461.3

DN100 pipe at 250 °C, 50 mm insulation, per metre of pipe; bare loss 826 W/m. λ at mean temperature; € and CO2 per metre·year at €0.05/kWh, 8000 h, 82% efficiency. Method: ASTM C680 simplified (h=10).

Material datasheet: Expanded perlite → · temperature class: by temperature →

FAQ

Questions on this topic

How much heat does a pipe at 250 °C lose with expanded perlite?
With 50 mm at 250 °C (λ=0.070 at mean): DN50 loses 94 W/m, DN100 145 W/m, DN200 240 W/m — vs 826 W/m bare for DN100. Full table on this page.
What surface temperature does expanded perlite give at 250 °C?
≈42 °C with 50 mm on DN100 (20 °C ambient, still air). Personnel-protection targets (≤45–60 °C) may need more thickness — see the 80/100 mm columns.