Inzonex Insulation Hubpowered by inzonex.co.uk
Insulation HubData tables → Ceramic fibre (RCF / AES blanket) at 500 °C
Computed datasheet

Ceramic fibre (RCF / AES blanket) at 500 °C — heat-loss table

λ = 0.069 W/m·K at mean temperature ((500+20)/2 = 260 °C, from the published curve). Pipe losses per metre, four thicknesses, savings vs bare.

Pipe30 mm W/m50 mm W/m80 mm W/m100 mm W/mBARE W/mSurface @50 mmSaving €/m·yr @50 mmt CO2/m·yr
DN2517714011410450453 °C€1770.65
DN5025819615313790959 °C€3481.27
DN803422521921701,34162 °C€5311.94
DN1004153002251971,72465 °C€6942.54
DN1505704022932542,53868 °C€1,0423.81
DN2007144963563053,30470 °C€1,3705.01
DN3001,0116904844104,88472 °C€2,0467.49

Assumptions: 20 °C ambient, still air (h=10 W/m²·K combined), €0.05/kWh fuel, 8000 h/yr, 82% efficiency, 0.183 kg CO2e/kWh (DESNZ 2024). Flat surfaces at this duty: bare 4,800 W/m² → 582 W/m² at 50 mm (≈€2,058/m²·yr saved). Method: ASTM C680 simplified — methodology. Your exact case: free calculator.

Context

All materials at 500 °C

Materialλ W/m·KLoss W/mSurfaceSaving €/m·yrt CO2/m·yr
Stone wool (mineral wool)0.07933970 °C€6752.5
Ceramic fibre (RCF / AES blanket)0.06930065 °C€6942.5
Aerogel blanket0.03817346 °C€7572.8
Calcium silicate0.08335673 °C€6672.4
Expanded perlite0.08636775 °C€6622.4
Microporous (fumed-silica) panels0.02511737 °C€7842.9
E-glass needle mat0.06829764 °C€6962.5
Silica needle mat / fabric0.06227461 °C€7072.6

DN100 pipe at 500 °C, 50 mm insulation, per metre of pipe; bare loss 1,724 W/m. λ at mean temperature; € and CO2 per metre·year at €0.05/kWh, 8000 h, 82% efficiency. Method: ASTM C680 simplified (h=10).

Material datasheet: Ceramic fibre (RCF / AES blanket) → · temperature class: by temperature →

FAQ

Questions on this topic

How much heat does a pipe at 500 °C lose with ceramic fibre (rcf / aes blanket)?
With 50 mm at 500 °C (λ=0.069 at mean): DN50 loses 196 W/m, DN100 300 W/m, DN200 496 W/m — vs 1,724 W/m bare for DN100. Full table on this page.
What surface temperature does ceramic fibre (rcf / aes blanket) give at 500 °C?
≈65 °C with 50 mm on DN100 (20 °C ambient, still air). Personnel-protection targets (≤45–60 °C) may need more thickness — see the 80/100 mm columns.