Inzonex Insulation Hubpowered by inzonex.co.uk
Insulation HubData tables → Calcium silicate at 600 °C
Computed datasheet

Calcium silicate at 600 °C — heat-loss table

λ = 0.090 W/m·K at mean temperature ((600+20)/2 = 310 °C, from the published curve). Pipe losses per metre, four thicknesses, savings vs bare.

Pipe30 mm W/m50 mm W/m80 mm W/m100 mm W/mBARE W/mSurface @50 mmSaving €/m·yr @50 mmt CO2/m·yr
DN2527021717816360972 °C€1910.70
DN503923022392151,09980 °C€3881.42
DN805173882992661,62085 °C€6012.20
DN1006274633503082,08389 °C€7902.89
DN1508586184563963,06793 °C€1,1954.37
DN2001,0757625534773,99296 °C€1,5765.77
DN3001,5191,0587526405,90299 °C€2,3638.65

Assumptions: 20 °C ambient, still air (h=10 W/m²·K combined), €0.05/kWh fuel, 8000 h/yr, 82% efficiency, 0.183 kg CO2e/kWh (DESNZ 2024). Flat surfaces at this duty: bare 5,800 W/m² → 889 W/m² at 50 mm (≈€2,396/m²·yr saved). Method: ASTM C680 simplified — methodology. Your exact case: free calculator.

Context

All materials at 600 °C

Materialλ W/m·KLoss W/mSurfaceSaving €/m·yrt CO2/m·yr
Stone wool (mineral wool)0.09247090 °C€7872.9
Ceramic fibre (RCF / AES blanket)0.07639879 °C€8223.0
Aerogel blanket0.04323655 °C€9013.3
Calcium silicate0.09046389 °C€7902.9
Expanded perlite0.09246990 °C€7872.9
Microporous (fumed-silica) panels0.02614642 °C€9453.5
Silica needle mat / fabric0.06936274 °C€8403.1

DN100 pipe at 600 °C, 50 mm insulation, per metre of pipe; bare loss 2,083 W/m. λ at mean temperature; € and CO2 per metre·year at €0.05/kWh, 8000 h, 82% efficiency. Method: ASTM C680 simplified (h=10).

Material datasheet: Calcium silicate → · temperature class: by temperature →

FAQ

Questions on this topic

How much heat does a pipe at 600 °C lose with calcium silicate?
With 50 mm at 600 °C (λ=0.090 at mean): DN50 loses 302 W/m, DN100 463 W/m, DN200 762 W/m — vs 2,083 W/m bare for DN100. Full table on this page.
What surface temperature does calcium silicate give at 600 °C?
≈89 °C with 50 mm on DN100 (20 °C ambient, still air). Personnel-protection targets (≤45–60 °C) may need more thickness — see the 80/100 mm columns.