BOILERS / METHOD / COMPARISONS

Boiler surface heat loss: surveyed components compared

Based on the published Boilers surveys and model outputs. Read the source scope alongside each comparison.

01 / COMPARISON

Published inputs and what they mean

Surveyed surfaceMetal °CModelled area m²Calculated bare WBare W/m²
Bosch UL-S front door962.332,5301,086
Cochran feed pump1001.491,6641,117
Cochran front door1205.327,9731,499
Cochran economiser12611.3118,3271,620
Cochran end plate1305.329,0631,704
Bosch burner flange1460.851,7802,094
Cochran check valve1800.902,5992,888
Bosch steam valves1900.451,4303,178

Cochran and Bosch are separate surveyed installations. These rows are not a controlled manufacturer comparison. Temperature, shape and component scope differ. W/m² separates the effect of area from total loss, but does not remove temperature or geometry effects.

The Cochran economiser contributes 18,327 W over 11.31 m². The Bosch burner flange contributes 1,780 W over 0.85 m². The flange has higher loss per square metre; the economiser is the larger total opportunity. Prioritise total recoverable heat together with access, coverage and installed cost.

Doors at their surveyed conditions

The Cochran door is 5.32 m² at 120 °C and 7,973 W bare; the Bosch UL-S door is 2.33 m² at 96 °C and 2,530 W bare. Their different total losses do not establish a difference in boiler efficiency. Neither figure represents the entire boiler.

Source rows: Cochran door, Bosch door and flange, Cochran end plate and economiser, feedwater surfaces, Cochran steam fittings and Bosch steam fittings.