INZONEX / COCHRAN SHELL BOILER · FEEDWATER & BLOWDOWN SIDE
UK · EU
ISO 12241 · EN ISO 13732-1

Boiler feed pump & feedwater heat loss

Boiler feed water is the water pumped into the shell to replace what leaves as steam. The feed and condensate side runs near 100 °C across the pump, isolation valves, return lines, strainer and blowdown — many small bare surfaces.

01 FLIR-MEASURED SURFACE TEMPS02 CAD AREAS × 1.4 BOLT/IRREGULARITY03 ISO 12241 · V = 0.5 M/S04 ISO 12241 HEAT-LOSS METHOD
€3,024energy cost saved / yr, at 60 €/MWh fuel
45 MWhheat kept in the boiler, 7,700 h/yr
10.2 tCO₂ avoided / yr, 201.6 kg/MWh
180  °CBare, FLIR-measured
01 / BARE AGAINST PANELLED

The same surface, both states

Figures are for one boiler. Surface temperatures from a real FLIR survey of a UK commercial boiler house; CAD surface areas uplifted ×1.4 for bolts and irregular geometry; ISO 12241 steady-state (50 mm core, ambient 28 °C, air movement 0.5 m/s).

Boiler feed pump & feedwater heat loss, bare
Bare as found
Boiler feed pump & feedwater heat loss, insulated
Insulated surface ≤45 °C

Drag-free toggle. Visible in this view: feed pump, globe valve, return lines, strainer and blowdown flanges — ~100 °C.3D model: Inzonex · equipment rights belong to the manufacturer

02 / WHAT YOU ARE LOOKING AT

Boiler feed pump & feedwater heat loss

No single surface here is dramatic, but the feedwater set is a cluster of a dozen-plus warm bodies at ~100 °C — a pump casing, valves, a strainer, return runs and blowdown connections. Each is left bare because it is “small” and needs access.

Added together they are a continuous loss worth insulating, and every one of them needs to stay serviceable. Removable covers and pipe sleeves insulate the set while keeping seals, handwheels, unions and the strainer basket reachable.

Element (this view)Temp °CArea m²Bare WInsulated WSurface °CCut
Feed pump1001.491,6648733−95%
Globe valve1000.364022133−95%
Return lines ×31000.819054833−95%
Feed piping ×81001.201,3407033−95%
Filter / strainer1000.364022133−95%
Blowdown flanges ×21800.521,5017639−95%
Feedwater & blowdown side view, per boiler4.76,214323≤45−95%

ISO 12241, 50 mm Inzonex modular core, ε(bare)=0.9, ε(jacket)=0.85, hconv at 0.5 m/s. Insulated figures are conservative steady-state.

03 / ELEMENT BY ELEMENT

Why each one is left bare — and how it gets insulated

Feed pump · 100 °C · 1.7 kW bare

The boiler feed pump body and its casing run near 100 °C. A removable cover insulates the volute while leaving the seal, bearings and coupling accessible for service.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Globe valve · 100 °C · 0.4 kW bare

Feed-line isolation valve at ~100 °C — another small cast body left bare. A shaped cover insulates it without seizing the handwheel.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Return lines · 100 °C · 0.9 kW bare

Condensate and return runs at ~100 °C. Individually minor, but several short bare sections in the feed set add up to real continuous loss.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Feed piping · 100 °C · 1.3 kW bare

Multiple short bare pipe sections around the feed set. Removable pipe sleeves insulate them and still allow union and flange access.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Filter / strainer · 100 °C · 0.4 kW bare

The feed strainer body sits at ~100 °C and must open for cleaning — a textbook case for a removable, re-openable cover rather than fixed lagging.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Blowdown flanges · 180 °C · 1.5 kW bare

Blowdown connections see boiler-pressure temperature in bursts and are left bare for safety access. A removable shroud insulates the standing loss while keeping the valve operable.

Cover: Silicone shell + PAROC stone-wool core (50 mm) · touch-safe design target ≤45 °C (ISO 13732-1 guidance)

Every module here re-opens for access.

04 / MATERIALS & STANDARDS

What the cover is — and what it meets

Every surface on this view is covered by an Inzonex modular removable panel: a PAROC stone-wool core (50 mm) in a silicone outer shell — or a more durable PTFE shell as an option. The form-fitting build unbuttons for access and refits after each maintenance cycle. The outer surface drops to a touch-safe ≤45 °C.

ISO 12241 heat-loss methodISO 13732-1 ≤45 °C touch-safeEN 13501-1 reaction to fireASTM C680 heat-loss method

Industries that run this boiler

Brewery & beverageFood processingDairySugar & confectioneryDistillingChemical & petrochemicalPharmaceuticalTextile & dyeingPaper, pulp & packagingRubber & tyrePlasticsTobaccoPower & CHPOil & gas / refiningHospitals & healthcareCommercial laundryHotels & hospitalityUniversities & district heatingEdible oilAnimal feed
05 / TAKE IT FURTHER

From this surface to the number that matters

06 / FAQ

Quick answers

Should a boiler feed pump be insulated?

The pump casing/volute can be insulated with a removable cover at ~100 °C, while the seal, bearings and coupling stay accessible. It removes a standing loss and a hot-touch hazard.

How hot is the feedwater side of a boiler?

On the surveyed Cochran the feed pump, valves, returns, strainer and blowdown ran near 100 °C.

Are small bare pipes worth insulating?

Individually no, collectively yes — a feed set of a dozen warm bodies is a continuous multi-hundred-watt loss, cut ~95% with removable sleeves and covers.

07 / COMBINATION

Watts per square metre

Selected readings from this boiler survey. This surface is the marked point.

04008001,2001,6002,0002,4002,8003,200100120140160180200W / m2SURFACE C1117feed pump1499front door1620economiser1704end plate2888check valveMeasured loss divided by CAD area, 5 Inzonex readings. ISO 12241:2022 steady state.
08 / METHOD

How every figure here was taken

Every figure on this page comes from the same chain: a radiometric camera reading of the surface, an area rebuilt in CAD from the surveyed machine, and an ISO 12241 calculation from those two. The instrument settings, the area allowance, the energy basis and the list of what was not measured are set out once, in full, on the method page.

The method, step by step →

09 / DEEPER

One level down from this view

10 / EVIDENCE

Where each number comes from

SurveyCochran, feedwater and blowdown side. FLIR S62 Pro, emissivity 0.90, reflected 25 °C, 3 m, full radiometric correction. Peak on this view 180  °C.
GeometryRebuilt in CAD from the surveyed machine. This view carries 6 element group(s) and sheds 6.2  kW bare. The ×1.4 factor is a geometry allowance for bolts, seams and irregular surface — it is not a measured area.
CalculationISO 12241 steady state. Heat loss is calculated from the measured surface temperature and the modelled area — it is not metered. Full method, basis and limits.
Largest single itemFeed pump, 1.7  kW on this view.
11 / SURFACE BY SURFACE

The other surveyed surfaces on this Cochran