InzonexHRSG unit
Lower IP line

Metal bellows

The lower IP detail starts from its own line duty and smaller metal-bellows geometry.

What is included

The calculation uses the lower IP geometry and does not reuse the hotter HP result.

Reference temperature200 °C
Starting quantity1 · enter your site count
Bare heat loss1.939 kW
With insulation0.078 kW
Heat retained1.862 kW
Reduction96%
Outside surface36.0 °C · target met
Temperature and quantity are editable. Energy rate, installed cost and payback remain blank until entered by the operator.

Why removable insulation matters

The module can be removed to expose the metal component and fasteners, then returned to the same position. This supports inspection without destroying and rebuilding the insulation each time.

Equipment-life boundary

Lower thermal exposure and repeatable inspection can support equipment care. A fixed life-extension figure needs component material, stress, cycling, drainage and inspection history.

Open this area in Your savings →